DAIKIN ROOM AIR CONDITIONERINSTALLATION MANUALR410A Split SeriesEnglishFrançaisEspañolMODELSFTXS15LVJUFTXS18LVJUFTXS24LVJU00_CV_3P297301-2.indd 1 10
English English 93-3. Wall embedded piping•Insertthedrainhosetothisdepthsoitwon’tbepulledoutofthedrainpipe.Inner wallVinyl chloride d
10 EnglishIndoor Unit Installation5. Drain piping1)Connectthedrainhose,asdescribedright.The drain hose should be inclined downward.No trap is
English English 11Trial Operation and Testing1. Trial operation and testing1-1 Measurethesupplyvoltageandmakesurethatitfallsinthespecie
12 EnglishMEMO01_EN_3P297301-2.indd 12 10/18/2011 2:00:52 PM
Two-dimensional bar code is a code for manufacturing.3P297301-2 M11B120(1111)HT00_CV_3P297301-2.indd 2 10/18/2011 10:19:50 AM
English English 1Safety Precautions•ReadtheseSafetyPrecautionscarefullytoensurecorrectinstallation.•Thismanualclassiestheprecautionsin
2 EnglishSafety Precautions WARNING•Duringpump-down,stopthecompressorbeforeremovingtherefrigerantpiping.Ifthecompressorisstillrunning
English English 3Indoor Unit Installation DrawingsBefore screwing the remote controller holder to the wall, make sure that control signals are properl
4 EnglishPreparation before Installation1. Removing and installing front panel•Removal methodHookngersonthetabsontheleftandrightofthem
English English 53. How to set the different addressesWhen2indoorunitsareinstalledinoneroom,the2wirelessremotecontrollerscanbesetfor
6 EnglishRefrigerant Piping Work2. Refrigerant pipingCAUTION•Usethearenutxedtothemainunittopreventitfromcrackinganddeterioratingf
English English 7Indoor Unit Installation1. Installing the mounting plate•Themountingplateshouldbeinstalledonawallwhichcansupportthewei
8 EnglishIndoor Unit Installation3. Laying piping, hoses, and wiring3-1. Right-side, right-back, or right-bottom piping 1)Attachthedrainhoseto