Note: Installationandmaintenancearetobeperformedonlybyqualiedpersonnelwhoarefamiliarwithlocalcodesandregulationsandareexperienc
IM 1193 / Page 10 of 32Thick Wall ConstructionA heavy-gauge, corrosion resistant wall sleeve is provided for each unit. The wall sleeve is either ship
IM 1193 / Page 11 of 32Figure 14: Attach hydronic coil blockoff plateUnderside of Hydronic Heat SectionScrews (2) ProvidedHydronic Coil Blockoff Plate
IM 1193 / Page 12 of 32Figure 15: Attach hydronic heat section to wall sleeveHeat section hooksWall Sleeve square holesHydronic Heat SectionPipingReco
IM 1193 / Page 13 of 32Installing The ValvePrior to soldering the normally closed two-way valve, open the ports by slowly moving the manual operating
IM 1193 / Page 14 of 32Supply and Return Coil ArrangementsSteamFigure 20: Left-hand supply and returnSupplyReturnFigure 21: Right-hand supply and retu
IM 1193 / Page 15 of 32Installing Cooling ChassisCorrect installation of the cooling chassis is extremely im-portant to insure the proper operation of
IM 1193 / Page 16 of 32Table 13: Voltage measurementsOperating VoltageUnit Voltage Voltage Utilization RangeRating Minimum Maximum230/208 197 253265
IM 1193 / Page 17 of 32Non-Programmable Electronic Thermostat (P/N 910140678)Non-Programmable, Auto Changeover, Fan Speed Control, Hardwired Single
IM 1193 / Page 18 of 32Operating InstructionsCooling or Heating – Manual Operation The PGAN unit controller has built-in features such as ran-dom star
IM 1193 / Page 19 of 32Simple to operate, single push button for one-stage heating and cooling, or single stage heat pump. Zone compatible and 4- or 5
IM 1193 / Page 2 of 32ContentsSafety Information ...3Inspection ...
IM 1193 / Page 20 of 32Standard Auto or Manual-Changeover Two-Stage Heat/ Two-Stage Cool SpecsPart No. 910116774 (1-Pk, White with Wall Plate)Specica
IM 1193 / Page 21 of 32Table 15: Internal control touchpad configuration settingsConguration Code Description Option Code DescriptionC1 Interface0* C
IM 1193 / Page 22 of 32Diagnostic Maintenance & Status Report - Internal Control TouchpadThe Diagnostic Maintenance & Status Report on the Int
IM 1193 / Page 23 of 32Table 16: Diagnostic codesCode Status DisplayError LightSuggested ActionModesFPFreeze Protection Engaged. The room temperaturem
IM 1193 / Page 24 of 32Adverse Operating Conditions MaintenanceUnits operating in dusty or corrosive locations; i.e. dusty construction site or sea co
IM 1193 / Page 25 of 32PTAC/PTHP Startup Report–AuditJob Name __________________________________________ City ________________ G.O. # ____________Ins
IM 1193 / Page 26 of 321. Blowers won’t operate on cool2. Blowers operate on cool but compressor does not start3. Blowers run on cool and c
IM 1193 / Page 27 of 32Notes:Thisguidewaspreparedwithstandardequipmentinmind.Ifequipmentisspecial,itmaynotbeentirelyapplicable.* If
IM 1193 / Page 28 of 32Wiring DiagramsPGAN with Hydronic HeatIO-44002/2013FOR A HEAT PUMPTHERMOSTAT USEDON A STRAIGHTCOOL UNITGL - LOW SPEEDGH - HIGH
IM 1193 / Page 29 of 32Wiring DiagramPGAN with Hydronic Heat, Power Vent and Power DoorIO-4412/2013FOR A HEAT PUMPTHERMOSTAT USEDON A STRAIGHTCOOL UNI
IM 1193 / Page 3 of 32Now that you have made an investment in modern, efcient Daikin® equipment, its care and operation should be a high prior-ity. F
IM 1193 / Page 30 of 32Wiring DiagramPGAN with Hydronic Heat, Variable Speed Condenser and Evaporator Fan MotorsIO-7882/2013CM COMPEMFCFHPSHTRRCCFRVCT
IM 1193 / Page 31 of 32Wiring DiagramPGAN with Hydronic Heat, Variable Speed Condenser, Evaporator Fan Motors, Power Vent and Door OptionIO-7892/2013C
© 2013 Daikin Applied Applied • www.DaikinAP.com • (800) 432–1342 IM 1193 / Page 32 of 32 (10/13)Daikin Training and DevelopmentNow that you have mad
IM 1193 / Page 4 of 32Daikin Model PGAN Product NomenclatureNote: ForIllustrationpurposesonly.Notalloptionsavailablewithallmodels.Damper Typ
IM 1193 / Page 5 of 32Unit DimensionsNote: Electricalrough-inshouldbelocatedbehindkickplate(removablefront)andbelowwallsleeve.Table 1: Ca
IM 1193 / Page 6 of 32Figure 2: Louver frame dimensions423/16" (1072mm)163/16" (411mm)33/4" (92mm)443/16" (1122mm)183/16" (10
IM 1193 / Page 7 of 32 CAUTION Do not drill holes in the base of the wall sleeve. Use shims between the wall and the wall sleeve to preve
IM 1193 / Page 8 of 32Applications utilizing eld supplied louvers require addi-tional considerations:1. Louvers supplied by others must have 70% fre
IM 1193 / Page 9 of 32Figure 9: 16" x 42" optional recessed louver wall sleeve with continuous flange and drip edge 16" 42" D**Lou