Daikin RXYSQ6M7V3B Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Climatiseurs à système divisé Daikin RXYSQ6M7V3B. 2 - Daikin City Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Technical Data

EEDEN12-200Air ConditionersVRV® Air-cooled Selection ProcedureTechnical Data

Page 2

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure8222 Selection in heating mode2 - 1 FlowchartCONDITIONSSELECTION OF INDO

Page 3 - TABLE OF CONTENTS

•VRV® Systems • Air cooled selection procedure9• Air-cooled selection procedure222 Selection in heating mode2 - 2 Step by step2 - 2 - 1 Design conditi

Page 4 - system based on cooling load

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure10222 Selection in heating mode2 - 2 Step by step2 - 2 - 7 Selection of

Page 5

•VRV® Systems • Air cooled selection procedure11• Air-cooled selection procedure222 Selection in heating mode2 - 3 Example2 - 3 - 1 Design conditions•

Page 6

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure12222 Selection in heating mode2 - 3 Example2 - 3 - 6 Define heating cap

Page 7

•VRV® Systems • Air cooled selection procedure13• Air-cooled selection procedure222 Selection in heating mode2 - 3 Example2 - 3 - 7 Selection of outdo

Page 8

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure14233 Capacity correction ratio3 - 1 VRV®III heat recovery with connecti

Page 9

•VRV® Systems • Air cooled selection procedure15• Air-cooled selection procedure233 Capacity correction ratio3 - 1 VRV®III heat recovery with connecti

Page 10 - 2 Selection in heating mode

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure16233 Capacity correction ratio3 - 1 VRV®III heat recovery with connecti

Page 11

•VRV® Systems • Air cooled selection procedure17• Air-cooled selection procedure233 Capacity correction ratio3 - 1 VRV®III heat recovery with connecti

Page 12

EEDEN12-200Air ConditionersVRV® Air-cooled Selection ProcedureTechnical Data

Page 13

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure18233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 14

•VRV® Systems • Air cooled selection procedure19• Air-cooled selection procedure233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 15

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure20233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 16 - 3 Capacity correction ratio

•VRV® Systems • Air cooled selection procedure21• Air-cooled selection procedure233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 17

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure22233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 18

•VRV® Systems • Air cooled selection procedure23• Air-cooled selection procedure233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 19

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure24233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 20

•VRV® Systems • Air cooled selection procedure25• Air-cooled selection procedure233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 21

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure26233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 22

•VRV® Systems • Air cooled selection procedure27• Air-cooled selection procedure233 Capacity correction ratio3 - 2 VRV®III heat recovery small footpri

Page 23

•VRV® Systems • Air-cooled selection procedure1• Air-cooled selection procedure1 Selection procedure VRV® system based on cooling load. . . . 2Flowch

Page 24

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure28233 Capacity correction ratio3 - 3 VRV®III heat recovery high COP comb

Page 25 - REYQ20,32,34P8

•VRV® Systems • Air cooled selection procedure29• Air-cooled selection procedure233 Capacity correction ratio3 - 3 VRV®III heat recovery high COP comb

Page 26

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure30233 Capacity correction ratio3 - 3 VRV®III heat recovery high COP comb

Page 27

•VRV® Systems • Air cooled selection procedure31• Air-cooled selection procedure233 Capacity correction ratio3 - 3 VRV®III heat recovery high COP comb

Page 28

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure32233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 29

•VRV® Systems • Air cooled selection procedure33• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 30

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure34233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 31

•VRV® Systems • Air cooled selection procedure35• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 32

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure36233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 33 - REYHQ24P

•VRV® Systems • Air cooled selection procedure37• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 34

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure2211 Selection procedure VRV® system based on cooling load1 - 1 Flowchar

Page 35

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure38233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 36

•VRV® Systems • Air cooled selection procedure39• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 37

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure40233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 38

•VRV® Systems • Air cooled selection procedure41• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 39

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure42233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 40

•VRV® Systems • Air cooled selection procedure43• Air-cooled selection procedure233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 41

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure44233 Capacity correction ratio3 - 4 VRV®III heat pump small footprint c

Page 42

•VRV® Systems • Air cooled selection procedure45• Air-cooled selection procedure233 Capacity correction ratio3 - 5 VRV®III heat pump high COP combinat

Page 43

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure46233 Capacity correction ratio3 - 5 VRV®III heat pump high COP combinat

Page 44

•VRV® Systems • Air cooled selection procedure47• Air-cooled selection procedure233 Capacity correction ratio3 - 5 VRV®III heat pump high COP combinat

Page 45

•VRV® Systems • Air cooled selection procedure3• Air-cooled selection procedure211 Selection procedure VRV® system based on cooling load1 - 2 Step by

Page 46

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure48233 Capacity correction ratio3 - 5 VRV®III heat pump high COP combinat

Page 47

•VRV® Systems • Air cooled selection procedure49• Air-cooled selection procedure233 Capacity correction ratio3 - 5 VRV®III heat pump high COP combinat

Page 48

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure50233 Capacity correction ratio3 - 6 VRV®III-S1. Rate of change in cooli

Page 49

•VRV® Systems • Air cooled selection procedure51• Air-cooled selection procedure233 Capacity correction ratio3 - 6 VRV®III-S1. Rate of change in cooli

Page 50

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure52233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 51

•VRV® Systems • Air cooled selection procedure53• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 52

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure54233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 53

•VRV® Systems • Air cooled selection procedure55• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 54

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure56233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 55

•VRV® Systems • Air cooled selection procedure57• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 56

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure4211 Selection procedure VRV® system based on cooling load1 - 2 Step by

Page 57

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure58233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 58

•VRV® Systems • Air cooled selection procedure59• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 59

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure60233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 60

•VRV® Systems • Air cooled selection procedure61• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 61

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure62233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 62

•VRV® Systems • Air cooled selection procedure63• Air-cooled selection procedure233 Capacity correction ratio3 - 7 VRV®III heating only&RUUHFWLRQ

Page 63

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure64244 Integrated heating capacity coefficientREYQ-P8/P9INTEGRATED HEATIN

Page 64

•VRV® Systems • Air cooled selection procedure65• Air-cooled selection procedure244 Integrated heating capacity coefficientREYHQ-PINTEGRATED HEATING C

Page 65

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure66244 Integrated heating capacity coefficientINTEGRATED HEATING CAPACITY

Page 66

•VRV® Systems • Air cooled selection procedure67• Air-cooled selection procedure244 Integrated heating capacity coefficientINTEGRATED HEATING CAPACITY

Page 67

•VRV® Systems • Air cooled selection procedure5• Air-cooled selection procedure211 Selection procedure VRV® system based on cooling load1 - 3 Example1

Page 68 - RXYQ5-54P

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure68244 Integrated heating capacity coefficientINTEGRATED HEATING CAPACITY

Page 69 - RXYHQ12-36P

•VRV® Systems • Air cooled selection procedure69• Air-cooled selection procedure244 Integrated heating capacity coefficient3TW30402NOTES1. The figure s

Page 70

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure70244 Integrated heating capacity coefficient3TW30402NOTES1. The figure s

Page 71 - Heating capacity

•VRV® Systems • Air cooled selection procedure71• Air-cooled selection procedure244 Integrated heating capacity coefficient5;<5437:127( 7

Page 72

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure72255 Refnet pipe systemsDISCHARGE GAS SIDE JUNCTIONSUCTION GAS SIDE JUN

Page 73 - 7:

•VRV® Systems • Air cooled selection procedure73• Air-cooled selection procedure255 Refnet pipe systemsDISCHARGE GAS SIDE JUNCTIONSUCTION GAS SIDE JUN

Page 74 - 5 Refnet pipe systems

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure74255 Refnet pipe systemsGas-side junctionBHFQ22P1007 BHFQ22P1517ID Ø31.

Page 75

•VRV® Systems • Air cooled selection procedure75• Air-cooled selection procedure255 Refnet pipe systemsSUCTION GAS SIDE JUNCTION DISCHARGE GAS SIDE JU

Page 76

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure76255 Refnet pipe systems2TW29119-1Gas side junctionLiquid side junction

Page 77

•VRV® Systems • Air cooled selection procedure77• Air-cooled selection procedure255 Refnet pipe systemsDISCHARGE GAS SIDE JUNCTIONSUCTION GAS SIDE JUN

Page 78

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure6211 Selection procedure VRV® system based on cooling load1 - 3 Example1

Page 79

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure78255 Refnet pipe systemsDISCHARGE GAS SIDE JUNCTIONSUCTION GAS SIDE JUN

Page 80

•VRV® Systems • Air cooled selection procedure79• Air-cooled selection procedure255 Refnet pipe systems2TW29659-1Gas-side junction Liquid side junctio

Page 81

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure80255 Refnet pipe systems2TW29679-1Suction gas side junction Discharge g

Page 82

•VRV® Systems • Air cooled selection procedure81• Air-cooled selection procedure255 Refnet pipe systemsGAS SIDE JUNCTION DISCHARGE GAS SIDE JUNCTION L

Page 83

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure82266 Example of Refnet piping layoutsType of fitting Sample systemsDist

Page 84

•VRV® Systems • Air cooled selection procedure83• Air-cooled selection procedure277 Refrigerant pipe selection7 - 1 VRV®III heat recovery small footpr

Page 85 - 7 Refrigerant pipe selection

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure84277 Refrigerant pipe selection7 - 1 VRV®III heat recovery small footpr

Page 86

•VRV® Systems • Air cooled selection procedure85• Air-cooled selection procedure277 Refrigerant pipe selection7 - 2 VRV®III heat recovery small footpr

Page 87

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure86277 Refrigerant pipe selection7 - 2 VRV®III heat recovery small footpr

Page 88

•VRV® Systems • Air cooled selection procedure87• Air-cooled selection procedure277 Refrigerant pipe selection7 - 3 VRV®III heat recovery with connect

Page 89

•VRV® Systems • Air cooled selection procedure7• Air-cooled selection procedure211 Selection procedure VRV® system based on cooling load1 - 3 Example1

Page 90

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure88277 Refrigerant pipe selection7 - 3 VRV®III heat recovery with connect

Page 91

•VRV® Systems • Air cooled selection procedure89• Air-cooled selection procedure277 Refrigerant pipe selection7 - 4 VRV®III heat pump small footprint

Page 92

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure90277 Refrigerant pipe selection7 - 4VRV®III heat pump small footprint c

Page 93

•VRV® Systems • Air cooled selection procedure91• Air-cooled selection procedure277 Refrigerant pipe selection7 - 5 VRV®III-Sab c d e fghi j kl mn1234

Page 94

• Air-cooled selection procedure•VRV® Systems • Air cooled selection procedure92277 Refrigerant pipe selection7 - 5 VRV®III-SBP 11 2 3ABBP 1BP 3faedcb

Page 95

•VRV® Systems • Air cooled selection procedure93• Air-cooled selection procedure277 Refrigerant pipe selection7 - 6 Piping thicknessO annealed1/2H hal

Page 96

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR OostendeEEDEN12-200 • CD • 04/12 • Cop

Commentaires sur ces manuels

Pas de commentaire