TECHNICAL MANUAL
Split Unit Air Conditioner
Ceiling Concealed Series
FDMRN-C, FDMQN-C Series
— Cooling only & Heatpump [50Hz] —
R410A
DAIKIN_FDMRN.indb iDAIKIN_FDMRN.indb i 1/8/2013 8:46:01 AM1/8/2013 8:46:01 AM
Vue de la page 0
1 2 3 4 5 6 ... 105 106

Résumé du contenu

Page 1 - TECHNICAL MANUAL

TECHNICAL MANUALSplit Unit Air ConditionerCeiling Concealed SeriesFDMRN-C, FDMQN-C Series— Cooling only & Heatpump [50Hz] —R410ADAIKIN_FDMRN.indb

Page 2

7Application Information Model: FDMRN100CXV1 – RR90/100DXV1FDMRN100/125/140CXV1 – RR90/100/125/140DXY1OUTDOOR UNITSTRAINERCOOLING OPERATION3 WAYVALV

Page 3 - Table of Contents

97Service & Maintenance Pre Start Up Maintenance(After Extended Shutdown)Q Inspect thoroughly and clean indoor and outdoor units.Q Clean or replac

Page 4 - Nomenclature

98 TroubleshootingTroubleshootingCooling / Heat pump ModelSeven Segments Faulty IndicationE1 Blinking Room air sensor contact loose/shortE2 Blinking

Page 5 - Product Line-Up

99Troubleshooting Error Code / Fault ConditionWhen a malfunction of the air conditioner unit is detected, immediately switch off the main power supply

Page 6

100 TroubleshootingDiagnostic GuidelinesBy means of pressure readings:DataCircuitPressureProbable causeToo lowA little lowNormalA little highToo high

Page 7 - Nomenclature

101Troubleshooting BY MEANS OF DIAGNOSTIC FLOW CHART :Generally, there are two kinds of problems, i.e. starting failure and insuffi cient cooling/heati

Page 8

102 Troubleshootingii) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not perform sa

Page 9 - Refrigerant Circuit Diagrams

DAIKIN_FDMRN.indb 103DAIKIN_FDMRN.indb 103 1/8/2013 8:46:17 AM1/8/2013 8:46:17 AM

Page 10 - Application Information

8 Application InformationModel: FDMQN35/50/60CXV1 – RYN35/50/60CXV1FDMQN50/60CXV1 – RYN50/60CXY1STRAINERSTRAINER3 WAYVALVE4 WAY VALVEPIPINGGASPIPING

Page 11 - FDMQN71CXV1 – RQ71CXY1

9Application Information Model: FDMQN100CXV1 – RQ90/100DXV1FDMQN100/125/140CXV1 – RQ90/100/125/140DXY1OUTDOOR UNITSTRAINER3 WAYVALVE4 WAY VALVEHIGHP

Page 12

10 Application InformationInstallation GuidelineSharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.(1) Installat

Page 13 - Installation Guideline

11Application Information (2) Installation of Outdoor UnitAs condensing temperature rises, evaporating temperature rises and cooling capacity drops.

Page 14 - Installation Clearance

12 Application Information(3) Cable SizeModel UnitFDMRN25CXV1 FDMRN35CXV1 FDMRN50CXV1 FDMRN60CXV1 FDMRN71CXV1RN25CXV1 RN35CXV1 RN50CXV1 RN60CXV1 RR71

Page 15 - (3) Cable Size

13Application Information (4) Refrigerant PipingWhen the pipe length becomes too long, both the capacity and reliability drop. As the number of bends

Page 16 - (4) Refrigerant Piping

14 Application Information(5) Additional ChargeThe refrigerant charge has already charged into the outdoor unit. For the piping length of 7.5m, addit

Page 17 - (5) Additional Charge

15Application Information (6) Special Precautions When Dealing With R410A UnitR410A is a new HFC refrigerant which does not damage the ozone layer. T

Page 18

16 Sound DataSound DataSound Pressure LevelModel Speed1/1 Octave Sound Pressure (dB, ref 20μPa)Overall (dBA)Noise Criteria125Hz 250Hz 500Hz 1kHz 2kH

Page 19 - Sound Data

DAIKIN_FDMRN.indb iiDAIKIN_FDMRN.indb ii 1/8/2013 8:46:02 AM1/8/2013 8:46:02 AM

Page 20 - Sound Power Level

17Sound Data Sound Power LevelModelExt. Static (mmAq)Speed1/1 Octave Sound Power (dB, ref 1pW)Overall (dBA)125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHzFDMRN

Page 21 - NC Curve

18 Sound DataNC CurveOctave-band frequency (Hz)Sound pressure level (dB, ref 20Pa)010203040506070125 250 500 1000 2000 4000 8000NC-20NC-25NC-30NC-35

Page 22 - FDMRN60CXV1 / FDMQN60CXV1

19Sound Data Sound pressure level (dB, ref 20Pa)010203040506070125 250 500 1000 2000 4000 8000NC-25NC-30NC-35NC-40NC-45NC-50HLNC-20MFDMRN50CXV1 / FD

Page 23 - FDMRN100CXV1 / FDMQN100CXV1

20 Sound Data010203040506070125250 500 1000 2000 4000 8000NC-30NC-35NC-40NC-45NC-50MLSHNC-25NC-20Sound pressure level (dB, ref 20Pa)FDMRN71CXV1 / FD

Page 24 - FDMRN140CXV1 / FDMQN140CXV1

21Sound Data Sound pressure level (dB, ref 20Pa)010203040506070125 250 500 1000 2000 4000 8000NC-20NC-25NC-35NC-40NC-45NC-50LSHMNC-30HFDMRN125CXV1 /

Page 25 - FDMRN25CXV1 / FDMQN25CXV1

22 Selection ProcessSelection ProcessBlower Performance CurveExternal Static Pressure (mm wg)0.00.51.01.52.02.53.03.5100200300 400Flowrate, (CFM)LMHF

Page 26 - FDMRN35CXV1 / FDMQN35CXV1

23Selection Process FDMRN35CXV1 / FDMQN35CXV1External Static Pressure (mm wg)LMH0.00.51.01.52.02.53.03.5300350400450500Flowrate, (CFM)DAIKIN_FDMRN.ind

Page 27

24 Selection ProcessFDMRN50CXV1 / FDMQN50CXV1External Static Pressure (mm wg)Flowrate, (CFM)LMH0.00.51.01.52.02.53.03.5400500600700DAIKIN_FDMRN.indb

Page 28

25Selection Process External Static Pressure (mm wg)Flowrate, (CFM)LMH0.00.51.01.52.02.53.03.5400500 600 700800FDMRN60CXV1 / FDMQN60CXV1DAIKIN_FDMRN.i

Page 29

26 Selection ProcessExternal Static Pressure (mm wg)Flowrate, (CFM)LMHSH02468101214200400 60080010001200FDMRN71CXV1 / FDMQN71CXV1DAIKIN_FDMRN.indb

Page 30

Table of ContentsTable of ContentsNomenclature...

Page 31

27Selection Process External Static Pressure (mm wg)Flowrate, (CFM)LMHSH0510156008001000120014001600FDMRN100CXV1 / FDMQN100CXV1DAIKIN_FDMRN.indb 27D

Page 32

28 Selection ProcessExternal Static Pressure (mm wg)Flowrate, (CFM)LMHSH05101520251000 1200140016001800FDMRN125CXV1 / FDMQN125CXV1DAIKIN_FDMRN.indb

Page 33

29Selection Process 220020001800160014001200External Static Pressure (mm wg)Flowrate, (CFM)LMHSH05101520251000FDMRN140CXV1 / FDMQN140CXV1DAIKIN_FDMRN.

Page 34

30 Engineering & Physical DataEngineering & Physical DataEngineering Data – R410A MODELMODELINDOOR UNIT FDMRN25CXV1 FDMRN35CXV1 FDMRN50CXV1 F

Page 35

31Engineering & Physical Data Engineering Data - R410A MODELMODELINDOOR UNIT FDMRN60CXV1 FDMRN60CXV1 FDMRN71CXV1 FDMRN71CXV1OUTDOOR UNIT RN60CXV1

Page 36

32 Engineering & Physical DataEngineering Data - R410A MODELMODELINDOOR UNIT FDMRN100CXV1 FDMRN100CXV1 FDMRN100CXV1 FDMRN100CXV1OUTDOOR UNIT RR90

Page 37 - Safety Device

33Engineering & Physical Data Engineering Data - R410A MODELMODELINDOOR UNIT FDMRN125CXV1 FDMRN140CXV1OUTDOOR UNIT RR125DXY1 RR140DXY1NOMINAL COO

Page 38

34 Engineering & Physical DataSafety DeviceMODELINDOORFDMRN25CXV1 FDMRN35CXV1 FDMRN50CXV1OUTDOORRN25CXV1 RN35CXV1 RN50CXV1SAFETY DEVICEHIGH PRESS

Page 39 - Performance Data

35Engineering & Physical Data MODELINDOORFDMQN25CXV1 FDMQN35CXV1 FDMQN50CXV1OUTDOORRYN25CXV1 RYN35CXV1 RYN50CXV1SAFETY DEVICEHIGH PRESSURE SWITCH

Page 40

36 Performance DataPerformance DataCalculation StepsInterpolation method can be used to get the total cooling capacity, TC and sensible cooling capac

Page 41 - R410A Cooling Only

Nomenclature 1NomenclatureIndoorFDM(R)(Q)N 25 C X V1Power SupplyV1: 1 phase 50 Hz 220-240VProductionX: OYLMProduct SeriesC: C SeriesCapacity25: 2.5kW

Page 42 - Cooling Mode

37Performance Data (b) Indoor Condition: 25°C DB, 16°C WBOutdoor Condition: 35°C DBEWB EDBOutdoor temperature35°CTC SC PI1924 3.51 2.57 1.2925x2y2z22

Page 43 - Model: FDMRN50CXV1 - RN50CXV1

38 Performance DataPerformance TablesR410A Cooling OnlyModel: FDMRN25CXV1 - RN25CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°

Page 44 - Model: FDMRN50CXV1 - RN50CXY1

39Performance Data Model: FDMRN35CXV1 - RN35CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 45 - Model: FDMRN60CXV1 - RN60CXV1

40 Performance DataModel: FDMRN50CXV1 - RN50CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 46 - Model: FDMRN60CXV1 - RN60CXY1

41Performance Data Model: FDMRN50CXV1 - RN50CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 47 - Model: FDMRN71CXV1 - RR71CXV1

42 Performance DataModel: FDMRN60CXV1 - RN60CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 48 - Model: FDMRN71CXV1 - RR71CXY1

43Performance Data Model: FDMRN60CXV1 - RN60CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 49

44 Performance DataModel: FDMRN71CXV1 - RR71CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 50

45Performance Data Model: FDMRN71CXV1 - RR71CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 51

46 Performance DataModel: FDMRN100CXV1 - RR90DXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 52

Nomenclature2Product Line-UpIndoor UnitFDMRN / FDMQNNomenclatureClassifi cationHandsetPCBFinRefrigerant ControlAir Purifi cationOthersBRC51A62BRC51A61

Page 53

47Performance Data Model: FDMRN100CXV1 - RR90DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 54

48 Performance DataModel: FDMRN100CXV1 - RR100DXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 55 - R410A Heatpump

49Performance Data Model: FDMRN100CXV1 - RR100DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 56 - Heating Mode

50 Performance DataModel: FDMRN125CXV1 - RR125DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 57

51Performance Data Model: FDMRN140CXV1 - RR140DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 58

52 Performance DataR410A HeatpumpModel: FDMQN25CXV1 - RYN25CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI T

Page 59

53Performance Data Model: FDMQN35CXV1 - RYN35CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 60

54 Performance DataModel: FDMQN50CXV1 - RYN50CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 61 - Model: FDMQN71CXV1 - RQ71CXV1

55Performance Data Model: FDMQN50CXV1 - RYN50CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 62

56 Performance DataModel: FDMQN60CXV1 - RYN60CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 63 - Model: FDMQN71CXV1 - RQ71CXY1

Nomenclature 3Outdoor UnitR(Y)N / RR / RQNomenclatureClassifi cationRefrigerant ControlFinSafety DevicesCompressorOthersCap TubeTXVHydrophilic (Blue)H

Page 64

57Performance Data Model: FDMQN60CXV1 - RYN60CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 65

58 Performance DataModel: FDMQN71CXV1 - RQ71CXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 66

59Performance Data Model: FDMQN71CXV1 - RQ71CXV1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC SC

Page 67

60 Performance DataModel: FDMQN71CXV1 - RQ71CXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC P

Page 68

61Performance Data Model: FDMQN71CXV1 - RQ71CXY1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC SC

Page 69

62 Performance DataModel: FDMQN100CXV1 - RQ90DXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 70

63Performance Data Model: FDMQN100CXV1 - RQ90DXV1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC S

Page 71

64 Performance DataModel: FDMQN100CXV1 - RQ90DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 72

65Performance Data Model: FDMQN100CXV1 - RQ90DXY1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC S

Page 73

66 Performance DataModel: FDMQN100CXV1 - RQ100DXV1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 74

Nomenclature4NomenclatureClassifi cationRefrigerant ControlFinSafety DevicesCompressorOthersCap TubeTXVHydrophilic (Blue)Hydrophilic (Gold)Bare Alumi

Page 75

67Performance Data Model: FDMQN100CXV1 - RQ100DXV1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC

Page 76

68 Performance DataModel: FDMQN100CXV1 - RQ100DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 77 - Outlines & Dimensions

69Performance Data Model: FDMQN100CXV1 - RQ100DXY1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC

Page 78 - Note: Dimension in mm

70 Performance DataModel: FDMQN125CXV1 - RQ125DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 79 - Outlines & Dimensions

71Performance Data Model: FDMQN125CXV1 - RQ125DXY1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC

Page 80 - Outdoor Unit

72 Performance DataModel: FDMQN140CXV1 - RQ140DXY1Cooling ModeAFR (CFM)EWB EDBOutdoor temperature19°C 25°C 30°C 35°C 40°C 46°CTC SC PI TC SC PI TC SC

Page 81

73Performance Data Model: FDMQN140CXV1 - RQ140DXY1Heating ModeID DBOutdoor WB-9°C -6°C -5°C 6°C 12°C 15°C 18°CTC SC TC SC TC SC TC SC TC SC TC SC TC

Page 82 - Wiring Diagrams

Outlines & Dimensions74Outlines & DimensionsIndoor UnitModel: FDMRN25CXV1 / FDMQN25CXV1Note: Dimension in mmModel: FDMRN35/50/60CXV1 / FDMQN

Page 83 - Model: RN50/60CXY1

Outlines & Dimensions 75Model: FDMRN71CXV1 / FDMQN71CXV1Note: Dimension in mmModel: FDMRN100CXV1 / FDMQN100CXV1Note: Dimension in mmDAIKIN_FDMRN.i

Page 84 - Model: RN50/60CXV1

Outlines & Dimensions76Model: FDMRN125/140CXV1 / FDMQN125/140CXV1DimensionModelABCDEFGH IFDMRN125CXV1 / FDMQN125CXV11299.0 1369.0 1326.0 1287.0

Page 85 - Model: RR71CXV1

5Application Information Application InformationOperating RangeEnsure the operating temperature is in allowable range.CoolingThe use of your air cond

Page 86 - Model: RR71CXY1

Outlines & Dimensions 77Outdoor UnitModel: R(Y)N25/35CXV1KLLAMBIGNOPRSJCNQHDEFDimensionModelABCDE FGH I JKLMNOPQRSR(Y)N25/35CXV1 700 521 250 478 1

Page 87 - Model: RR90/100DXV1

Outlines & Dimensions78Model: RR90/100DXV1 / RQ90/100DXV1 / RR90/100/125/140DXY1 / RQ90/100/125/140DXY1MADE IN MALAYSIAIJJDMBGONNKALEFHCDimensio

Page 88 - Model: RR90/100/125DXY1

79Wiring Diagrams Wiring DiagramsCooling OnlyIndoor UnitModel: FDMRN25/35CXV1Outdoor UnitModel: RN25/35CXV1DAIKIN_FDMRN.indb 79DAIKIN_FDMRN.indb

Page 89 - Model: RR140DXY1

80 Wiring DiagramsIndoor UnitModel: FDMRN50/60CXV1Outdoor UnitModel: RN50/60CXY1DAIKIN_FDMRN.indb 80DAIKIN_FDMRN.indb 80 1/8/2013 8:46:14 AM1/8

Page 90 - Heatpump

81Wiring Diagrams Indoor UnitModel: FDMRN50/60CXV1Outdoor UnitModel: RN50/60CXV1DAIKIN_FDMRN.indb 81DAIKIN_FDMRN.indb 81 1/8/2013 8:46:14 AM1/8

Page 91 - Model: RYN50/60CXY1

82 Wiring DiagramsIndoor UnitModel: FDMRN71CXV1Outdoor UnitModel: RR71CXV1DAIKIN_FDMRN.indb 82DAIKIN_FDMRN.indb 82 1/8/2013 8:46:14 AM1/8/2013

Page 92 - Model: RYN50/60CXV1

83Wiring Diagrams Indoor UnitModel: FDMRN71CXV1Outdoor UnitModel: RR71CXY1DAIKIN_FDMRN.indb 83DAIKIN_FDMRN.indb 83 1/8/2013 8:46:14 AM1/8/2013

Page 93 - Model: FDMQN71CXV1

84 Wiring DiagramsIndoor UnitModel: FDMRN100CXV1Outdoor UnitModel: RR90/100DXV1DAIKIN_FDMRN.indb 84DAIKIN_FDMRN.indb 84 1/8/2013 8:46:14 AM1/8/

Page 94

85Wiring Diagrams Indoor UnitModel: FDMRN100/125CXV1Outdoor UnitModel: RR90/100/125DXY1DAIKIN_FDMRN.indb 85DAIKIN_FDMRN.indb 85 1/8/2013 8:46:1

Page 95 - Model: RQ90DXV1

86 Wiring DiagramsIndoor UnitModel: FDMRN140CXV1Outdoor UnitModel: RR140DXY1DAIKIN_FDMRN.indb 86DAIKIN_FDMRN.indb 86 1/8/2013 8:46:15 AM1/8/201

Page 96 - Model: RQ100DXV1

6 Application InformationRefrigerant Circuit DiagramsModel: FDMRN25/35/50/60CXV1 – RN25/35/50/60CXV1FDMRN50/60CXV1 – RN50/60CXY1COOLING OPERATION3 W

Page 97 - Model: RQ90/100/125DXY1

87Wiring Diagrams HeatpumpIndoor UnitModel: FDMQN25/35CXV1Outdoor UnitModel: RYN25/35CXV1DAIKIN_FDMRN.indb 87DAIKIN_FDMRN.indb 87 1/8/2013 8:46

Page 98 - Model: RQ140DXY1

88 Wiring DiagramsIndoor UnitModel: FDMQN50/60CXV1Outdoor UnitModel: RYN50/60CXY1DAIKIN_FDMRN.indb 88DAIKIN_FDMRN.indb 88 1/8/2013 8:46:15 AM1/

Page 99 - Service & Maintenance

89Wiring Diagrams Indoor UnitModel: FDMQN50/60CXV1Outdoor UnitModel: RYN50/60CXV1DAIKIN_FDMRN.indb 89DAIKIN_FDMRN.indb 89 1/8/2013 8:46:15 AM1/

Page 100 - Pre Start Up Maintenance

90 Wiring DiagramsIndoor UnitModel: FDMQN71CXV1Outdoor UnitModel: RR71CXV1DAIKIN_FDMRN.indb 90DAIKIN_FDMRN.indb 90 1/8/2013 8:46:15 AM1/8/2013

Page 101 - Troubleshooting

91Wiring Diagrams Indoor UnitModel: FDMQN71CXV1Outdoor UnitModel: RR71CXY1DAIKIN_FDMRN.indb 91DAIKIN_FDMRN.indb 91 1/8/2013 8:46:15 AM1/8/2013

Page 102 - Error Code / Fault Condition

92 Wiring DiagramsIndoor UnitModel: FDMQN100CXV1Outdoor UnitModel: RQ90DXV1DAIKIN_FDMRN.indb 92DAIKIN_FDMRN.indb 92 1/8/2013 8:46:15 AM1/8/2013

Page 103 - Troubleshooting

93Wiring Diagrams Indoor UnitModel: FDMQN100CXV1Outdoor UnitModel: RQ100DXV1DAIKIN_FDMRN.indb 93DAIKIN_FDMRN.indb 93 1/8/2013 8:46:16 AM1/8/201

Page 104

94 Wiring DiagramsIndoor UnitModel: FDMQN100/125CXV1Outdoor UnitModel: RQ90/100/125DXY1DAIKIN_FDMRN.indb 94DAIKIN_FDMRN.indb 94 1/8/2013 8:46:1

Page 105

95Wiring Diagrams Indoor UnitModel: FDMQN140CXV1Outdoor UnitModel: RQ140DXY1DAIKIN_FDMRN.indb 95DAIKIN_FDMRN.indb 95 1/8/2013 8:46:16 AM1/8/201

Page 106

96 Service & MaintenanceService & MaintenanceDisconnect from main supply before servicing the air conditioner.The unit is designed to give lo