■English 2
Accessories
– ,
*1 The thermistor cable is attached to the indoor unit.
Choosing a Site
• Before choosing the installation site, obtain user approval.
Installation Tips
■
■■
■
How to remove the front panel.
•
Hook fingers on the panel protrusions on the left and right of the main body, and open until the panel stops.
•
Slide the front panel sideways to disengage the rotating shaft.
•
Then pull the front panel toward you to remove it.
■
■■
■
How to attach the front panel.
•
Align the tabs of the front panel with the grooves, and push all the way in.
•
Then close slowly.
•
Push the center of the lower surface of the panel firmly to engage the tabs.
■
■■
■
How to remove the front grille.
•
Open the front panel.
•
Remove the screws (2 pcs) on the front grille.
•
Pull the lower part of the front grille toward you, then remove the front grille completely.
(There are 2 hooks on the upper part.)
If it is difficult to remove, open the front grille and raise the top grid, using a screwdriver,
to unhook the hooks.
■
■■
■
How to attach the front grille.
•
Attach the front grille to the bottom frame, and lock the upper hooks (2points) securely.
•
Tighten the screws (2 pcs) on the front grille.
•
Attach the front panel and close the front panel.
■
■■
■
How to set the different addresses.
•
When two indoor units are installed in one room, the two wireless remote con-
trollers can be set for different addresses.
■
■■
■
PCB in the indoor unit.
•
Remove the front panel.
•
Remove the electric parts box (1-screw).
•
Slide the metalic cover to remove it. (4-claws on the electric parts box)
•
Cut the jumper JA on PCB.
■
■■
■
Wireless remote controller.
•
Cut the jumper J4.
Mounting plate
1
Remote controller holder
1
Thermistor cable (8m)*1
1
Mounting plate fixing screw
M4 × 25L
6
Fixing screw for remote
controller holder M3 × 20L
2
Operation manual
1
Titanium Apatite Photocatalytic
Air-Purifying Filter
2
AAA dry-cell batteries
2
Installation manual
1
Wireless remote controller
1
Indoor unit fixing screw
M4 × 12L
2
Drain plug
(Heat pump-Models)
1
The indoor unit should be sited in a place where:
• the restrictions on installation specified in the
indoor unit installation drawings are met,
•
both air intake and exhaust have clear paths met,
• the unit is not in the path of direct sunlight,
•
the unit is away from the source of heat or steam,
• there is no source of machine oil vapour (this
may shorten indoor unit life),
• cool (heat) air is circulated throughout the room,
• the unit is away from electronic ignition type flu-
orescent lamps (inverter or rapid start type) as
they may shorten the remote control range,
• the unit is at least 1 metre away from any televi-
sion or radio set (unit may cause interference
with the picture or sound).
The outdoor unit should be sited in a place where:
•
the restrictions on installation specified in the outdoor unit installation diagram are met,
• drain water causes no trouble or problem in particular,
• both air intake and exhaust have clear paths of air (they should be free of
snow in snowy districts),
• the unit is in a clear path of air but not directly exposed to rain, strong
winds, or direct sunlight,
• there is no fear of inflammable gas leakage,
• the unit is no directly exposed to salt, sulfidized gases, or machine oil
vapour (they may shorten outdoor unit life),
• operation noise or hot air flow does not cause trouble to neighbours,
• the unit is at least 3 metres away from any television or radio antenna.
•
Turn on all the fluorescent lamps in the room, if any, and find the site where remote
controller signals are properly received by the indoor unit (within 7 metres).
A L
Outdoor unit
M
A E J
B F
K
C
G L
D
H M
Outdoor unit
Fit the key into the slot.
Filter guide
Screwdriver
Upper grille
Raise and
remove
Hook
Screwdriver
Upper hook
J4
ADDRESS
EXIST 1
CUT 2
J4
CUT 2
ADDRESS: JA
EXIST 1
JA
JC
C1
C31
J30
JP11
ADDRESS
Metallic
cover
Claws (4 point)
Electric
parts
box
PCB
Wireless
remote
controller
01_EN_3P147083-2F.fm Page 2 Friday, October 28, 2005 9:29 AM