General Functionality Si04-115
38 Main Function
1.17 Compressor Protection Function
Outline An refrigeration oil level descent and progression of the dilution which will arise at operation of
the compressors will be avoided by controlling the upper limit of frequency at the edge of
compressor’s changeover from OFF to ON as follows.
Processing
1. A choice of a constant based on the starting conditions.
A constant is chosen in the following conditions at the start of compressors.
In case TCG0 < TDEN
A type starting is adopted.
In case TCG0
TDEN
B type starting is adopted.
TCG0 is set only at power-ON and then start, keep counting regardless of the operation mode.
The judge above should be done only at the start of compressors.
TCG : Timer guard for compressor protection
TDEN : Elapsed time after power-on
2. Frequency control
The following control is carried out after the judge of 1. above. A constant is chosen in
accordance with A, B decided in 1).
Timer TCG1 (A,B) will start at the start of compressors.
The upper limit of output frequency in between TCG1 (A,B) is set at FCG1 (A,B).
In exceeding TCG1 (A,B), timer TCG2 (A,B) starts and the upper limit of output frequency in
between TCG2 (A,B) is set at FCG2(A,B).
In exceeding TCG2 (A,B), timer TCG3 (A,B) starts and the upper limit of output frequency in
between TCG3 (A,B) is set at FCG3(A,B).
In exceeding TCG3 (A,B), the frequency limit is cancelled.
3. Others
If compressors go off at the start of this function, the timer under counting should be reset
and cancelled the frequency limit.
This function doesn’t work under the control of defrosting.
FCG : Frequency guard for compressor protection
TCG : Timer guard for compressor protection
Setting a constant J type Setting a constant J type
FCG1A 46 Hz TCG1A 120 sec
FCG1B 46 Hz TCG1B 120 sec
FCG2A 66 Hz TCG2A 570 sec
FCG2B 66 Hz TCG2B 360 sec
FCG3A 90 Hz TCG3A 120 sec
FCG3B 80 Hz TCG3B 180 sec
TDEN 30 min
T CG3
T CG2T CG1
T CG0
Compressor operation frequency
time
F CG1
F CG2
F CG3
Power ON
(R1907)