Daikin EKHBH030BA Manuel d'installation Page 10

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 136
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 9
Installation manual
8
EKHBH/X030BA
Indoor unit for air to water heat pump system
4PW62568-1 – 07.2010
Application 6
Space heating with room thermostat application through floor heating
loops and fan coil units. The floor heating loops and fan coil units
require different operating water temperatures.
The floor heating loops require a lower water temperature in heating
mode compared to fan coil units. To achive these two set points, a
mixing station is used to adapt the water temperature according to
requirements of the floor heating loops. The fan coil units are directly
connected to the indoor unit water circuit and the floor heating loops
after the mixing station. The control of this mixing station is not done
by the indoor unit.
The operation and configuration of the field water circuit is the
responsibility of the installer.
Daikin only offers a dual set point control function. By this function
two set points can be generated. Depending on the required water
temperature (floor heating loops and/or fan coil units are required)
first set point or second set point can be activated.
Pump operation and space heating
When the room thermostat for the floor heating loop (T1) and the fan
coil units (T2) are connected to the indoor unit, the pump (4) will
operate when there is a request for heating from T1 and/or T2. The
outdoor unit will start operating to achieve the target leaving water
temperature. The target leaving water temperature depends on which
room thermostat is requesting heating.
When the room temperature of both zones is above the thermostat
set point, the outdoor unit and pump will stop operating.
1 Outdoor unit 8 Shut-off valve
2 Indoor unit 9 Mixing station (field supply)
3 Heat exchanger T1 Room thermostat for zone
A (optional)
4 Pump
5 Shut-off valve T2 Room thermostat for zone
B (optional)
6 Collector zone A
(field supply) FCU1..3 Fan coil unit (optional)
7 Collector zone B
(field supply)
FHL1...3 Floor heating loop
(field supply)
The advantage of the dual set point control is that the heat
pump will/can operate at the lowest required leaving water
temperature when only floor heating is required. Higher
leaving water temperatures are only required in case fan
coil units are operating.
This results in a better performance of the heat pump.
FHL1
FHL2
FHL3
T1
T2
FCU1
FCU2
FCU3
54321
8 9
7
6
B
A
Set point Field setting Thermo status
Zone A First UI ON OFF ON OFF
Zone B Second [7-03] OFF ON ON OFF
Resulting water temperature UI [7-03] [7-03]
Result pump operation ON ON ON OFF
NOTE
Make sure to connect the thermostat wires to the
correct terminals (see "Overview of the indoor
unit" on page 9).
Make sure to configure the field settings [7-02],
[7-03] and [7-04] correctly. Refer to "Dual set point
control" on page 30.
Make sure to configure the DIP switch SS2-3 on
the PCB of the EKHBH switch box correctly. Refer
to "Room thermostat installation configuration" on
page 23.
NOTE
The request signals for space heating can be
implemented in two different ways (installer
choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the
mixing station
It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high
water temperatures towards floor heating loops,
etc.)
Daikin does not offer any type of mixing station.
Dual set point control only provides the possibility
to use two set points.
When only zone A request heating, zone B will be
fed with water at a temperature equal to the first
set point.
This can lead to unwanted heating of zone B.
When only zone B request heating, the mixing
station will be fed with water at a temperature
equal to the second set point.
Depending on the control of the mixing station,
the floor heating loop can still receive water at a
temperature equal to set point of the mixing
station.
Be aware that the actual water temperature through the
floor heating loops depends on the control and setting of
the mixing station.
4PW62568-1.book Page 8 Wednesday, June 30, 2010 12:02 PM
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 135 136

Commentaires sur ces manuels

Pas de commentaire