FXZQ Specifications
15
ABSOLUTE COMFORT
www.daikinac.com
FXZQ Specifications 0.6-Ton 0.75-Ton 1-Ton 1.5-Ton
Model Name FXZQ07M7VJU FXZQ09M7VJU FXZQ12M7VJU FXZQ18M7VJU
Power Supply V/ph/Hz 208-230/1/60
Cooling Capacity Btu/h 7,500 9,500 12,000 18,000
Heating Capacity Btu/h 8,700 11,100 14,000 21,000
Refrigerant R-410A R-410A R-410A R-410A
Refrigerant Control Electronic Expansion Valve
Airflow Rate H/L cfm 320/247 335/265 495/353 495/353
Unit Weight lbs. 42 42 42 42
Unit Height in. 11 1/4 11 1/4 11 1/4 11 1/4
Unit Width in. 22 5/8 22 5/8 22 5/8 22 5/8
Unit Depth in. 22 5/8 22 5/8 22 5/8 22 5/8
Sound Pressure H/L dB(A) 31/29 33/29 41/34 41/34
Unit Condensate Connection in. O.D. 1 1/32 1 1/32 1 1/32 1 1/32
Condensate Pump Lift in. 21 1/2 21 1/2 21 1/2 21 1/2
Pipe Connections
Liquid in. 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare
Gas in. 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare
External Finish Galvanized Steel Plate
Protection Devices
Fuse
Fan Motor Thermal Protector
Recommended Fuse/Breaker A 15 15 15 15
Standard Filter Type Resin Net (with Mold Resistant)
FXZQ Accessories
Model Name FXZQ07M7VJU FXZQ09M7VJU FXZQ12M7VJU FXZQ18M7VJU
Navigation Remote Controller BRC1E71 BRC1E71 BRC1E71 BRC1E71
Simplified Wired Remote Controller* BRC2A71 BRC2A71 BRC2A71 BRC2A71
Remote Sensor Kit KRCS01-1B KRCS01-1B KRCS01-1B KRCS01-1B
Decoration Panel BYFQ60BU BYFQ60BU BYFQ60BU BYFQ60BU
Wiring Adaptor PCB
(interface with aux/primary heater, humidifier, OA damper/fan)
KRP1B72 KRP1B72 KRP1B72 KRP1B72
Long-Life Replacement Filter KAFQ441B60 KAFQ441B60 KAFQ441B60 KAFQ441B60
Sealing Member of Air Discharge Outlet KDBHQ44B60 KDBHQ44B60 KDBHQ44B60 KDBHQ44B60
Panel Spacer KDBQ44B60 KDBQ44B60 KDBQ44B60 KDBQ44B60
Fresh Air Intake Kit KDDQ44XA60 KDDQ44XA60 KDDQ44XA60 KDDQ44XA60
* Optional face plates available to provide a more intuitive user interface and disable specific functions
FXZQ Installation Space
(NOTE) Leave 7 7/8 or more space where marked with the *, on sides where the air outlet is closed.
(length: in.)
*59 or more *59 or more
H
Air inlet
Air discharge
Air discharge
*59 or more *59 or more
H
Air inlet
Air dischargeAir discharge
Model
FXZQ07-18M7VJU
H
11.6 or more
INDOOR
Nominal Conditions: Cooling Mode Heating Mode Note:
Indoor: 80 °F DB / 67 °F WB Indoor: 70 °F DB Specifications are subject to change without notice.
Outdoor: 95 °F DB Outdoor: 47 °F DB / 43 °F WB
Pipe Length: 25 ft. Pipe Length: 25 ft.
Level Difference: 0 ft. Level Difference: 0 ft.