Water-cooled design guide
VRV Systems Water-cooled design guide
38
1
7
7 Typical VRV-WIII installations
7 - 4 Example Installation
(With heat recovery from multiple systems through water circuit)
Temperature indicating controller
T2
RWEY
PTPT
R R R
To BS unit
RWEY
PTPT
R RR
RWEY
PTPT
R RR
To BS unit
Temperature indicating controller
T3
Temperature indicating controller
T1
V1
V2
V3
Part A
V5
V4
V6
To BS unit
RWEY
PTPT
R RR
RWEY
PTPT
R RR
RWEY
PTPT
R R R
RWEY
PTPT
R R R
RWEY
PTPT
R R R
To BS unit
Expansion tank
P
T
F
Pump
Temperature controller
Y strainer
Flexible joint
Pressure gauge
Thermometer
Flow switch
V1
V2
V3
V4
V5
V6
Operation mode
T1 set value
T2 set value
Open:
Closed:
T3 set value
F
Use a hermestic cooling tower in terms of water quality control
Makeup water
(Used to fill the
tank as well)
In order to use brine for the freezing protection, install the
heat exchanger to break off the line concerned.
Cooling tower (32°C/37°C)
In order to provide two or more hydrothermal systems (e.g. mainly heating for the
north side system and mainly cooling on the south side), integrate the multiple
systems into a single system, thus allowing for the heat recovery even between the
water vs. water systems.
Makeup water
(Used to fill the
tank as well)
On each floor, If 1 multiple units are installed or 2 the units
are installed far away from each other, use horizontal reverse
return piping or a constant flow control valve to prevent air
drift.
It is recommended to provide a port used
for the cleaning of horizontal drain pipes.
For RWEY models, provide interlock with the flow switch.
(Through the pump operation signal, an operative flow
switch is recommended.)
Three-way valve (mixed type)
Cooling
(mainly for cooling)
Heating
(mainly for cooling)
In-between seasons
(cooling/heating combination)
15°C 25°C
20°C40°C
33°C, 31°C33°C, 31°C
Open/Closed
of valve